Outback-power-systems GS3548E Operators Manual Manual de usuario Pagina 71

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 76
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 70
Specifications
900-0145-01-01 Rev A 69
Table 16 Radian Inverter Settings
Field Item Default Minimum Maximum
Inverter Stacking
Stack Mode Master Master, Slave, B Phase Master, C Phase Master
Power Save
Ranking
Mode = Master: Master Power Save Level
0 0 31
Mode = Slave: Slave Power Save Level
1 1 31
Mode = B Phase Master Master Power Save Level
0 0 31
Mode = C Phase Master: Master Power Save Level
0 0 31
Grid-Tie Sell
Grid-Tie Enable Y Y or N
Sell Voltage
52.0 Vdc 44.0 Vdc 64.0 Vdc
Module Control
Module Control
GS7048E
Auto
Auto, Left, Right, Both
GS3548E
Left Auto, Left, Right, Both
Calibrate
Grid AC Input Voltage X
0 Vac –7 Vac 7 Vac
Gen AC Input Voltage X
0 Vac –7 Vac 7 Vac
Output Voltage X
0 Vac –7 Vac 7 Vac
Battery Voltage X
0.0 Vdc 0.8 Vdc 0.8 Vdc
Grid Interface Protection Menu
Operating Frequency
Operating Frequency X
50 Hz 50 Hz, 60 Hz
Stage 1 Voltage Trip
Over Voltage Clearance Time X
1.5 seconds 0.12 seconds 4.0 seconds
Over Voltage Trip X
252 Vac 240 Vac 300 Vac
Under Voltage Clearance Time X
1.5 seconds 0.12 seconds 4.0 seconds
Under Voltage Trip X
208 Vac 160 Vac 240 Vac
Stage 2 Voltage Trip
Over Voltage Clearance Time X
0.2 seconds 0.12 seconds 4.0 seconds
Over Voltage Trip X
264 Vac 240 Vac 300 Vac
Under Voltage Clearance Time X
0.2 seconds 0.12 seconds 4.0 seconds
Under Voltage Trip X
196 Vac 160 Vac 240 Vac
Frequency Trip
Over Frequency
Clearance Time
X
0.2 seconds 0.12 seconds 5.0 seconds
Over
Frequency
Trip
50-Hz system
X
51.0 Hz 50.1 Hz 55.0 Hz
60-Hz system 61.0 Hz 60.1 Hz 65.0 Hz
Under Frequency
Clearance Time
X
0.2 seconds 0.12 seconds 5.0 seconds
Under
Frequency
Trip
50-Hz system
X
47.0 Hz 45.0 Hz 49.9 Hz
60-Hz system 57.0 Hz 55.0 Hz 59.9 Hz
Mains Loss
Clearance Time X
2.0 seconds 1.0 seconds 5.0 seconds
Reconnect Delay X
300 seconds 2 seconds 302 seconds
Sell Current Limit
Maximum
Sell Current
GS7048E
X
30 Aac 5 Aac 30 Aac
GS3548E
15 Aac
5 Aac
15 Aac
Vista de pagina 70
1 2 ... 66 67 68 69 70 71 72 73 74 75 76