Specifications
66 900-0161-01-00 Rev A
Table 16 Radian Inverter Settings
Field Item Default Minimum Maximum
Gen AC Input
Mode and Limits
Input Mode Generator
Generator, Support, Grid Tied, UPS, Backup,
Mini Grid, Grid Zero
Voltage Limit Lower
108 Vac 85 Vac 110 Vac
(Voltage Limit) Upper
140Vac 125 Vac 140 Vac
Transfer Delay
1.0 second 0.12 seconds 4.0 seconds
Connect Delay
0.5 minutes 0.2 minutes 25.0 minutes
If Mini Grid mode
is selected:
Connect to Grid
48.0 Vdc 44.0 Vdc 64.0 Vdc
(Connect) Delay
10 minutes 2 minutes 200 minutes
If Grid Zero mode
is selected:
DoD Volts
48.0 Vdc 44.0 Vdc 64.0 Vdc
DoD
Amps
GS8048A
5 Aac 1 Aac 30 Aac
GS4048A
5 Aac 1 Aac 15 Aac
AC Output
Output Voltage X
120 Vac 100 Vac 130 Vac
AC Coupled Mode
This selection is inoperative
Low Battery
Cut-Out Voltage
42.0 Vdc
36.0 Vdc
48.0 Vdc
Cut-In Voltage
50.0 Vdc
40.0 Vdc
56.0 Vdc
Battery Charger
Absorb Voltage
57.6 Vdc 44.0 Vdc 64.0 Vdc
(Absorb) Time
1.0 hours
0.0 hours
24.0 hours
Float Voltage
54.4 Vdc
44.0 Vdc
64.0 Vdc
(Float)
Time
1.0 hours 0.0 hours 24/7
Re-Float Voltage
50.0 Vdc
44.0 Vdc
64.0 Vdc
Re-Bulk Voltage
49.6 Vdc 44.0 Vdc 64.0 Vdc
Battery Equalize
Equalize Voltage
58.4 Vdc
44.0 Vdc
68.0 Vdc
(Equalize) Time
1.0 hours
0.0 hours
24.0 hours
Auxiliary Output
Aux Control
Auto
Off, Auto
or
On
Aux Mode Vent Fan
Load Shed, Gen Alert, Fault, Vent Fan, Cool Fan,
DC Divert, GT Limits, Source Status, AC Divert
(Load Shed)
ON: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(Load Shed ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Load Shed)
OFF: Batt <
44.0 Vdc 40.0 Vdc 56.0 Vdc
(Load Shed OFF) Delay
0.5 minutes
0.1 minutes
25.0 minutes
(Gen Alert) ON: Batt <
44.0 Vdc 40.0 Vdc 56.0 Vdc
(Gen Alert ON)
Delay
0.5 minutes
0.1 minutes
25.0 minutes
(Gen Alert) OFF: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(Gen Alert OFF)
Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Vent Fan) ON: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(Vent Fan) Off Delay
0.5 minutes
0.1 minutes
25.0 minutes
(DC Divert)
ON: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(DC Divert ON) Delay
0.5 minutes
0.1 minutes
25.0 minutes
(DC Divert) OFF: Batt <
44.0 Vdc 40.0 Vdc 56.0 Vdc
(DC Divert OFF) Delay
0.5 minutes
0.1 minutes
25.0 minutes
(AC Divert) ON: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(AC Divert ON)
Delay
0.5 minutes
0.1 minutes
25.0 minutes
(AC Divert) OFF: Batt <
44.0 Vdc 40.0 Vdc 56.0 Vdc
(AC Divert OFF)
Delay
0.5 minutes 0.1 minutes 25.0 minutes
Auxiliary
Relay
Aux Control
Auto
Off, Auto or On
Aux Mode
Gen Alert
Load Shed, Gen Alert, Fault, Vent Fan, Cool Fan,
DC Divert, GT Limits, Source Status, AC Divert
(Load Shed) ON: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(Load Shed ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Load Shed) OFF: Batt <
44.0 Vdc
40.0 Vdc
56.0 Vdc
(Load Shed OFF) Delay
0.5 minutes
0.1 minutes
25.0 minutes
(Gen Alert)
ON: Batt <
44.0 Vdc
40.0 Vdc
56.0 Vdc
(Gen Alert ON) Delay
0.5 minutes
0.1 minutes
25.0 minutes