Table 16 Radian Inverter Settings
Field Item Default Minimum Maximum
(DC Divert)
56.0 Vdc 40.0 Vdc 72.0 Vdc
44.0 Vdc 40.0 Vdc 56.0 Vdc
(AC Divert) ON: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(AC Divert ON)
0.5 minutes 0.1 minutes 25.0 minutes
0.5 minutes 0.1 minutes 25.0 minutes
Inverter Stacking
Stack Mode Master Master, Slave
Power Save
Ranking
Mode =
:
1 1 31
Grid-Tie Sell
Module Control
Module Control
GS8048A Auto Auto, Left, Right, Both
Calibrate
0 Vac –7 Vac 7 Vac
Output Voltage X 0 Vac –7 Vac 7 Vac
0.0 Vdc –0.8 Vdc 0.8 Vdc
Grid Interface Protection Menu
Over Voltage Clearance Time X 1.0 seconds 0.12 seconds 5.0 seconds
Over Voltage Trip X 132 Vac 120 Vac 150 Vac
Under Voltage Clearance Time
Over Voltage Clearance Time
0.16 seconds 0.12 seconds 5.0 seconds
Over Voltage Trip X 144 vac 120 Vac 150 Vac
Under Voltage Clearance Time X 0.16 seconds 0.12 seconds 5.0 seconds
Over Frequency
Clearance Time
X
0.16 seconds 0.12 seconds 5.0 seconds
Over
Frequency
Trip
60-Hz system
X
60.5 Hz 60.1 Hz 65.0 Hz
50-Hz system 50.5 Hz 50.1 Hz 55.0 Hz
Under Frequency
Clearance Time
X
0.16 seconds 0.12 seconds 5.0 seconds
Under
Frequency
Trip
60-Hz system
X
59.3 Hz 55.0 Hz 59.9 Hz
50-Hz system 49.3 Hz 45.0 Hz 49.9 Hz
Mains Loss
Clearance Time X
2.0 seconds 1.0 seconds 5.0 seconds
300 seconds 2 seconds 302 seconds
Sell Current Limit
Sell Current
X