NOTE:eMATE’shbx-use
grid setpoint screen vdc value
willequalthesystemsbattery
voltage.Inthiscase,itreects
12VDCbatteries.Othervalues:
24VDCbattery—26.0 vdc;
32VDC—34.7 vdc;36VDC—
39.0 vdc;and48VDC—52 vdc.
MATE ADVANCED Default Values
ADV/MATE/HBX--------------------
hbx-use 12.0 vdc
grid setpoint
DOWN ADV INC DEC
ADV/MATE/HBX--------------------
hbx-drop 13.0 vdc
grid setpoint
DOWN ADV INC DEC
ADV/MATE/HBX--------------------
hbx-use 1.0 hrs
grid delay
DOWN ADV INC DEC
ADV/MATE/HBX---------------------
hbx-drop 1.0 hrs
grid delay
DOWN ADV INC DEC
• GriduseMenu
ADV/MATE/GRIDUSE-----
griduse enable: OFF
DOWN ADV OFF ON
ADV/MATE/GRIDUSE-----
weekday 12:00A
griduse stop time
DOWN UP CHANGE
ADV/MATE/GRIDUSE-----
weekday 12:00A
griduse start time
DOWN UP CHANGE
ADV/MATE/GRIDUSE-----
weekend 12:00A
griduse start time
DOWN UP CHANGE
ADV/MATE/GRIDUSE-----
weekend 12:00A
griduse stop time
DOWN UP CHANGE
• HBXMenu
• AGSSETUPMenu
MATE/AGS/SETUP------------------
ags port: 0
DOWN AGS INC DEC
ADV/MATE/AGS/SETUP------------
AGS control: MAN-OFF
DOWN UP CHANGE
ADV/MATE/AGS/SETUP------------
AGS enabled: No
DOWN UP NO YES
ADV/MATE/AGS/SETUP--------------
dc genset:: No
DOWN UP NO YES
ADV/MATE/AGS/SETUP-------------
ags fault 17 min
time
DOWN UP INC DEC
ADV/MATE/AGS/SETUP------------
vdc genstop 19.0 vdc
DOWN UP INC DEC
ADV/MATE/AGS/SETUP-------------
warm up time 0
minutes
DOWN UP INC DEC
ADV/MATE/AGS/SETUP------------
cool down time 0
minutes
DOWN UP INC DEC
ADV/MATE/HBX---------------------
ac input USE
control
DOWN UP CHANGE