101
ADV/MATE/AGS/QT----------------
weekday 12:00A
quiet time start
DOWN AGS CHANGE
ADV/MATE/AGS/QT------------------
weekend 12:00A
quiet time start
DOWN UP CHANGE
ADV/MATE/AGS/QT----------------
weekday 12:00A
quiet time stop
DOWN UP CHANGE
ADV/MATE/AGS/QT------------------
weekend 12:00A
quiet time stop
DOWN UP CHANGE
• AGSQUIETTIMEMenu
• AGSVOLTSTARTMenu
ADV/MATE/AGS/VSTART----------
volt start 12.2 vdc
24 hr setting
DOWN AGS INC DEC
ADV/MATE/AGS/VSTART------------
volt start 11.0 vdc
2 min setting
DOWN AGS INC DEC
ADV/MATE/AGS/VSTART-----------
volt start 11.8 vdc
2 hr setting
DOWN AGS INC DEC
Voltstart24hrsetting:
24VDCsystem=24.4vdc
32VDCsystem=32.6vdc
36VDCsystem=36.6vdc
48VDSsystem=48.8vdc
Voltstart2hrsetting:
24VDCsystem=23.6vdc
32VDCsystem=31.5vdc
36VDCsystem=35.4vdc
48VDSsystem=47.2vdc
Voltstart2minsetting:
24VDCsystem=22.0vdc
32VDCsystem=29.3vdc
36VDCsystem=33.0vdc
48VDSsystem=44.0vdc
• AGSLOADSTARTMenu
ADV/MATE/AGS/LS-----------------
load start 0 kw
DOWN AGS INC DEC
ADV/MATE/AGS/LS-----------------
load stop 0 kw
DOWN AGS INC DEC
ADV/MATE/AGS/LS-----------------
load start 1 min
delay
DOWN AGS INC DEC
ADV/MATE/AGS/LS-----
load stop 1 min
delay
DOWN AGS INC DEC